Maintenance & Cleaning
Low effort, but not zero
Frequently asked questions
55 questions on policy and payback, choosing a system, warranty, maintenance, the environment, installation troubleshooting and safety.
Net billing, incentives, payback and price
Type, size and what to expect
What is covered and for how long
Low effort, but not zero
Honest answers to hard questions
Design and workmanship points
Detailed answers on strings, cables, insulation, CT, meter and system control
Keep every panel in one series string on the same orientation and tilt, and give each roof face its own MPPT input.
In a series string the current is set by the weakest panel, so one shaded or differently-facing panel drags the whole string down.
Replace the damaged section with proper PV cable and connectors; never repair it with tape.
A string can carry several hundred volts DC whenever there is daylight, and a damaged cable can arc, start a fire or cause an insulation fault.
Find the one string, then the one panel, connector or cable that leaks to earth, and replace it; never disable the inverter's insulation protection.
Inverters show this as "PV ISO Fault", "DC Insulation Impedance Failure" or "Low Insulation Resistance" depending on brand.
Yes for a plain on-grid inverter that is allowed to export; no for a hybrid inverter or any system that must limit export.
The CT is the inverter's only way to see how much power the building is taking from or sending to the grid.
| System | Without CT | Result |
|---|---|---|
| On-grid, export allowed | Works | Produces at full power; extra goes to the grid |
| On-grid, zero export required | Not acceptable | Inverter cannot limit export; energy leaks to the grid |
| Hybrid with battery | Works poorly | Battery cannot follow the load; it may not discharge at night, or may export from battery |
| Hybrid in backup / off-grid mode only | Works | Supplies backup loads; no self-consumption control |
The inverter makes the opposite or a random decision: it exports when it should not, or charges the battery from the grid, and the monitoring data becomes wrong.
| Mistake | What the inverter sees | Typical symptoms |
|---|---|---|
| CT reversed (arrow wrong way, or S1/S2 swapped) | Grid import looks like export | Zero-export system exports at full power; inverter curtails while the house is importing; battery charges from grid; load shows negative or impossible values |
| CT on the wrong phase | Current from one phase against voltage of another (120° apart) | Readings too low, wrong sign or jumping; export control unstable |
| CT on the inverter output instead of the grid cable | Only its own output | Load always equals PV; export never controlled |
| CT on the neutral, or around both L and N | Near zero | Inverter thinks the house uses nothing |
Yes, as long as the inverter has a working CT (for models that support a direct CT) or export control is not needed.
A smart meter does the same job as a CT — it tells the inverter the grid power — but measures more accurately and talks to the inverter over RS485.
If the meter loses communication, most inverters either lose export control or cut output to zero for safety; check the RS485 wiring (A/B polarity), Modbus address and baud rate.
Use a smart meter whenever accuracy, distance or three phases matter.
Power flowing back to the grid when it should not is almost always a CT or meter installation error, or export limit not switched on.
Exporting without a sell-back agreement means giving energy away free, and may break the utility's connection conditions.
| Cause | Fix |
|---|---|
| CT arrow facing the wrong way, or S1/S2 swapped | Flip the CT or swap the leads; or reverse CT direction in settings |
| Meter L and N swapped, or CT on wrong meter terminals | Rewire to the meter's wiring diagram |
| CT installed downstream of the inverter connection point | Move it to the incoming grid cable, between utility meter and all loads plus inverter |
| Export limit / zero export not enabled | Enable it and set the limit to 0 W (or the permitted value) |
| Sudden large load switching off | Short export spikes of a few seconds are normal while the inverter reacts |
After fixing, repeat the known-load test and watch the utility meter during a sunny hour with low load.
In three-phase, each of the three CTs must sit on the same phase as the voltage it is paired with, and face the right way.
There are 6 ways to arrange three CTs across three phases and 8 combinations of directions — 48 possible installations, and only one is correct.
System control is how the inverter decides where solar, battery and grid power go; set it at commissioning to match the customer's goal and the utility's rules, then lock it.
| Mode | What it does | Best for |
|---|---|---|
| Self-use / Self-consumption | Solar feeds loads first, then battery, then grid | Most homes and businesses with battery |
| Feed-in priority | Exports first, keeps battery for later | Sites with a sell-back agreement |
| Backup / Reserve | Keeps battery at a set SOC for outages | Sites with frequent power cuts |
| Time-of-use (TOU) | Charges or discharges at set times | TOU tariff customers |
| Off-grid | Runs without grid | Remote sites |
| Peak shaving | Uses battery to cap grid import | Commercial sites with demand charges |
Surge, earthing and fire safety
| Type II SPD | AC side | DC side (solar PV) |
|---|---|---|
| Standard | IEC 61643-11 | IEC/EN 61643-31 |
| Test waveform | 8/20 µs | 8/20 µs |
| Nominal discharge current (In) | 5 to 20 kA (20 kA common) | 20 kA |
| Maximum current (Imax) | 40 to 80 kA | 40 kA or more |
| Where installed | Sub-distribution board / MDB | Combiner box / inverter DC input |
| Continuous voltage (Uc / Ucpv) | 275, 320 or 420 V AC | 600 or 1000 V DC, at or above string Voc |
Policy figures as of October 2026. Rates, quotas and incentives change; savings, payback and warranty figures are typical ranges, not guarantees. Your quotation states the exact terms for your system.